Jubail Industrial City, Saudi Arabia
LinkedIn🇸🇦 شركة نسناس الغربي التجارية
Sun–Thu: 8am–5pm
Electrical Engineering

Electrical Cable Sizing & De-Rating Factors for Extreme Middle East Ambient Conditions

Eng. Tariq Al-Mansoor (Senior Electrical Applications Specialist)
March 02, 2025
8 min read
Electrical Cable Sizing & De-Rating Factors for Extreme Middle East Ambient Conditions
Engineering principles for calculating current-carrying capacity, solar radiation de-rating, and soil thermal resistivity in Saudi industrial cable installations.

## The Challenge of Desert Heat on Cable ampacity

Standard cable manufacturer data sheets typically list current carrying capacities (ampacity) based on European baseline conditions: **30°C in air and 20°C in ground**.

In Saudi Arabia, ambient air temperatures frequently hit **50°C in the shade**, cable trays exposed to direct desert sunlight can reach **70°C**, and ground temperatures at 1-meter burial depth exceed **35°C–40°C**.

Failing to apply accurate de-rating factors leads to insulation thermal degradation, accelerated aging, dielectric breakdown, and dangerous electrical fires.


Crucial De-Rating Factors According to IEC 60287 / SEC Standards

$$I_{corrected} = I_{table} \times k_1 \times k_2 \times k_3 \times k_4$$

  • **$k_1$ (Ambient Temperature Correction Factor):** For XLPE insulated cables (rated 90°C conductor), operating at 50°C air temperature results in a de-rating factor of approximately **0.82**. At 60°C, the factor drops to **0.71**.
  • **$k_2$ (Direct Solar Radiation Factor):** Black sheathed cables in open outdoor trays absorb intense solar radiation. A further 10% to 15% de-rating is required unless sunshades are installed.
  • **$k_3$ (Soil Thermal Resistivity):** Saudi dry sandy soil has high thermal resistivity ($G = 2.0 \text{ to } 3.0 \text{ K}\cdot\text{m/W}$) compared to standard moist soil ($G = 1.0$). This significantly impedes underground heat dissipation.
  • **$k_4$ (Grouping / Proximity Factor):** Parallel multi-core cables in close touching contact generate mutual heating, requiring down-rating up to 40%.

Recommended Cable Specifications for KSA

  • **Insulation:** Cross-Linked Polyethylene (XLPE) or EPR rated for 90°C continuous / 250°C short circuit.
  • **Outer Sheath:** Heavy-duty UV-stabilized, hydrocarbon-resistant, Low Smoke Zero Halogen (LSZH) or flame retardant PVC.
  • **Armoring:** Steel Wire Armor (SWA) for multi-core cables, Aluminum Wire Armor (AWA) for single-core cables to prevent eddy current heating.

*West Wind stocks SASO and SEC-approved power, control, and instrumentation cables ready for dispatch in Jubail.*

Related Topic Tags:
#Cables#IEC 60287#Electrical Engineering#Saudi Arabia#Power Distribution
Article Author

Eng. Tariq Al-Mansoor

Senior Electrical Applications Specialist

Senior technical application specialist at West Wind Trading Co., specializing in industrial equipment compliance and engineering sourcing across Saudi Arabia.

Need Equipment Specified in this Article?

Contact our Jubail technical desk for sizing calculations, product datasheets, and official quotation.

Submit Inquiry